MMA highlights electrical safety failures following offshore incidents

The US Marine Minerals Administration (MMA) has issued a safety alert following multiple electrical incidents involving cable arcing, arc flashes and fires at offshore and marine facilities.
The safety alert identifies recurring deficiencies in electrical installation, inspection, maintenance and safe work practices. Contributing factors included insulation failure, improper installation, inadequate maintenance and exposure to harsh marine environments.
The MMA emphasized the importance of strengthening electrical design, installation and maintenance practices.
Incidents
The MMA highlighted three incidents involving electrical equipment and cable failures:
- Portable tool cable arc: A portable floor-preparation tool experienced electrical arcing when its worn power cable was flexed under load. The tool had not undergone a pre-use inspection and lacked ground-fault circuit interrupter (GFCI) protection in a conductive environment.
- Compressor motor cable arc flash: During a motor replacement, a worker mistakenly cut an energized cable belonging to another circuit. Lockout/tagout (LOTO) procedures were incomplete, and the absence of voltage had not been verified before work began.
- Control panel cable fire: An improperly routed cable and damaged ground lug caused chafing, overheating and an electrical fire. The installation also lacked adequate strain relief and showed evidence of mechanical damage.
Findings
The MMA’s review identified several recurring safety deficiencies:
- Electrical work was performed without establishing electrically safe working conditions, including incomplete LOTO procedures and failure to verify the absence of voltage.
- Job safety planning and briefings were not documented, while electrical shock and arc-flash risk assessments were inadequate.
- Cables, lugs, terminations and strain relief arrangements were damaged or poorly maintained, with insufficient inspections and missing GFCI protection in wet or conductive locations.
- Improper cable selection and routing increased exposure to mechanical and environmental damage, while inadequate sealing allowed moisture or flammable gases to enter enclosures.
- Overcurrent protection devices were not always properly rated or coordinated, and electrical diagrams and equipment labels were outdated.
- Inadequate grounding and bonding increased the potential for stray currents and electrical arcing.
Recommendations
Following its review, the MMA recommended that operators and contractors consider the following measures, where appropriate, to strengthen electrical safety and prevent similar incidents.
Design and installation controls
- Select marine-rated cables appropriate for the operating environment and application, considering armored or impervious-sheathed cables in hazardous or wet locations.
- Install approved cable seals at electrical enclosure entries where required by applicable National Electrical Code (NEC) provisions.
- Ensure cable terminations follow manufacturer instructions, including torque specifications, conductor preparation and minimum bend radius.
- Properly ground and bond cable armor, electrical enclosures and metallic sheaths in accordance with applicable standards.
Circuit protection and coordination
- Ensure overcurrent protection devices are appropriately sized for the electrical system and comply with applicable NEC requirements.
- Evaluate protection coordination and available fault currents to minimize equipment damage, system disruption and arc-flash energy.
- Consider current-limiting protective devices, including appropriate fuses, to reduce fault current and arc-flash incident energy.
Inspection, testing and maintenance
- Establish regular inspection schedules and pre-use checks for portable electrical equipment. Remove defective equipment from service and clearly label it as unsafe for use.
- Conduct periodic insulation resistance tests and inspect cables, terminals, lugs and enclosures for corrosion, chafing and mechanical damage.
- Repair or replace deteriorated components, maintain equipment according to manufacturer instructions and keep electrical diagrams and maintenance records updated.
Environmental and operational controls
- Route cables away from mechanical hazards, hot surfaces, chemicals, abrasion, vibration and other sources of potential damage.
- Use compatible fittings, adapters and thread types, avoiding combinations of metric and National Pipe Taper (NPT) threads.
- Where appropriate, install suitable space heaters or breathers to prevent condensation inside electrical enclosures.
- Provide adequate strain relief at cable and cord terminations to prevent excessive bending and mechanical loading.
- Install appropriate GFCI protection, particularly in wet or electrically conductive environments.
The MMA clarified that GFCIs protect against electric shock caused by ground-fault leakage, while arc-fault circuit interrupters (AFCIs) detect arcing faults. Arc-flash risks require additional engineered protection measures, such as current-limiting fuses.
NFPA 70E electrical safety practices
- Establish an electrical safety program incorporating assessments of electrical shock and arc-flash hazards.
- Ensure equipment is placed in an electrically safe condition before work begins by identifying circuits, isolating energy sources, applying LOTO procedures and verifying the absence of voltage.
- Do not rely solely on circuit labels, drawings or control room indications to confirm equipment is de-energized. Use an appropriately rated meter and verify its operation against a known live source before and after testing.
- Establish appropriate electrical safety boundaries, select personal protective equipment based on incident energy or the applicable arc-flash category, and maintain required equipment labeling.
- Ensure personnel carrying out electrical work are appropriately trained and qualified, with retraining at intervals not exceeding three years and whenever conditions warrant. Conduct work-practice audits to verify compliance.
The MMA emphasized that operators should consult the latest applicable editions of relevant electrical safety standards and guidance to ensure their procedures remain aligned with current requirements and recommended practices.